[ 4 ] Function data
Table 5.6 Function code and data (S08 to S11)
Code
Name
S08
Acceleration
time F07
S09
Deceleration
time F08
S10
Torque limit level
(Driving)
S11
Torque limit level
(Braking)
1) When an attempt is made to enter a value out of the permissible range, an out-of-range error
will result.
2) The acceleration/deceleration times specified with S08 and S09 are set to F07 (Acceleration
time 1) and F08 (Deceleration time 1). The torque limit levels specified with S10 and S11 are
set to F40 (Torque limit level (Driving)) and F41 (Torque limit level (Braking)). If the function
codes are changed through the keypad, etc., the changes are also reflected to S08 to S11.
3) The figures below the fourth place figure of the S08 acceleration time and the S09
deceleration time are omitted within the inverter. (If, for example, 123.4 s is written, 123.0 s
is entered.)
[ 5 ] Universal DO and universal AO
Code
Name
S07
Universal DO Command from
S12
Universal AO Command from
1) A host can control the output terminal of the inverter through the communications function to
issue commands to peripheral devices.
2) When universal DO and universal AO are assigned to the following signals, the signals
operate as simple output regardless of inverter's operation.
Universal DO: Transistor output (Y1, Y2, Y3, Y4), relay output (Y5A/C, 30A/B/C)
Universal AO: Analog output (FMA), pulse output (FMP)
Function
Set data with
common code
numbers and in
common
communications
formats to models.
* Legends in R/W column...R: Readable, W: Writable, R/W: Readable/writable
Table 5.7 Function code and data (S07, S12)
Function
communications
function to terminal DO
communications
function to terminal AO
* Legends in R/W column...R: Readable, W: Writable, R/W: Readable/writable
5-10
Permissible setting
Min. step
range
0.0 to 3600.0
0.0 to 3600.0
0.01
20.00 to 150.00,
999
0.01
20.00 to 150.00,
999
Permissible setting
Min. step
range
0000
to FFFF
H
H
-32768 to 32767
(Full scale by
±20000)
Unit
R/W *
0.1
s
R/W
0.1
s
R/W
%
R/W
%
R/W
Unit
R/W *
1
R/W
1
R/W