Fuji Electric FRENIC-AQUA series User Manual page 90

Rs-485 communication
Hide thumbs Also See for FRENIC-AQUA series:
Table of Contents

Advertisement

Code
Name
S31
Ext PID
PID command issued
command 1
through
communications
S32
Ext PID
PID command issued
command 2
through
communications
S33
Ext PID
PID command issued
command 3
through
communications
S90
Current
Clock time setting
year/month
through
communications
S91
Current day/hour Clock time setting
through
communications
S92
Current
Clock time setting
minute/second
through
communications
S93
Clock setting
Clock time setting
through
communications
5.1 Communications Dedicated Function Codes
Table 5.2 List of command data (Continued)
Permissible setting
Function
range
-32768 to 32767
(+/- 20000
corresponds to +/-
100%)
-32768 to 32767
(+/- 20000
corresponds to +/-
100%)
-32768 to 32767
(+/- 20000
corresponds to +/-
100%)
2012 to 2099
January to
December
1st to 31st
0 to 23 o'clock
0 to 59 minutes
0 to 59 seconds
0: Deactivate
1: Write
* Legends in R/W column...R: Readable, W: Writable, R/W: Readable/writable
5-3
Support
In units
Unit
R/W *
of
HVAC AQUA
1
R/W
1
R/W
1
R/W
1
R/W
1
R/W
1
R/W
1
R/W