Table 5.12 Keypad-related function code (W codes) (Continued)
Code
Name
W28
Operation command
source
W29
Frequency and PID
command source
W30
Speed set value at
percentage
W31
Speed set value at
percentage
W32
PID output
W33
Analog input monitor
*1 Operation command source code
Indicates the current source of operation commands.
Code
0
Run by the keypad
(rotation direction: depends on the terminal input)
1
Run by the terminals
2
Run by the keypad (forward rotation)
3
Run by the keypad (reverse rotation)
4
Run command 2 (when FR2/FR1 is ON)
5
Forced operation (Fire mode)
20
Port 1 (RS-485 channel 1) (Note)
21
Port 2 (RS-485 channel 2) (Note)
22
Bus option
23
Loader
5.1 Communications Dedicated Function Codes
Monitor range
Min step
0 to 23
1
0 to 39
1
0.00 to 100.00
0.01
0.00 to 100.00
0.01
-150.0 to 150.0
0.1
-999 to 9990
Variable
Description
5-17
Support
Unit
Remarks
HVAC/AQUA
*1
*2
%
%
%
PID output
expressed by a
percentage with
setting the
maximum
frequency (F03)
to 100%
Inverter's
analog input
converted by
E40 and E41
HVAC/AQUA
×

Advertisement

Table of Contents
loading

This manual is also suitable for:

Frenic-hvac series

Table of Contents