Point Mapping Tables - Fuji Electric FRENIC-AQUA series User Manual

Rs-485 communication
Hide thumbs Also See for FRENIC-AQUA series:
Table of Contents

Advertisement

6.3

Point Mapping Tables

Accessing the FRENIC-HVAC/AQUA through a Metasys N2 network requires registering point
maps to the Metasys.
AI: Analog input
BI: Bit input
AO: Analog output
BO: Bit output
AI and BI point mapping table
NPT NPA
Units
AI
1
Hz
AI
2
%
AI
3
%
AI
4
%
AI
5
Vrms
AI
6
-
AI
7
-
AI
8
-
AI
9
-
AI
10
h
AI
11
kWh
AI
12
-
AI
13
-
AI
14
-
AI
15
-
AI
16
A
AI
17
kW
BI
1
-
BI
2
-
BI
3
-
BI
4
-
BI
5
-
BI
6
-
BI
7
-
BI
8
-
BI
9
-
BI
10
-
BI
11
-
BI
12
-
BI
13
-
BI
14
-
BI
15
-
BI
16
-
BI
17
-
BI
18
-
Description
Output frequency
Output torque
Output current
Motor output
Output voltage
Alarm history (Latest)
Alarm history (Last)
PID output value
PID feedback value
Cumulative run time
Watt-hour
Control terminal [12]
Input voltage
Control terminal [C1]
Input current
Control terminal [V2]
Input voltage
Parameter data read
Output current
Motor output
FWD
REV
Trip
Frequency arrival signal
FAR
Frequency detection FDT
Inverter ready to run RDY
Reserved.
Reserved.
Current limiter active
In acceleration
In deceleration
Remote/local
Y1 terminal
Y2 terminal
Y3 terminal
Y4 terminal
Y5 terminal
30ABC terminal
6-3
6.3 Point Mapping Tables
Range
Notes
0 to 655.35
M09
-327.68 to 327.67
M07
0 to 399.99
M11
-327.68 to 327.67
M64
0.0 to 1000.0
M12
0 to 255
M16
0 to 255
M17
-32768 to 32767
M73, 20000 = 100%
-32768 to 32767
M72, 20000 = 100%
0 to 65535
M20
0.001 to 9999
W81
-32768 to 32767
M49, 20000 = 10 V
0 to 32767
M50, 20000 = 20 mA
-32768 to 32767
M54, 20000 = 10 V
float
0.00 to 9999
W05
0.00 to 9999
W22
0/1 = Off/On
M14 bit 0
0/1 = Off/On
M14 bit 1
0/1 = Off/On
M14 bit 11
0/1 = Off/On
M70 bit 0
0/1 = Off/On
M70 bit 1
0/1 = Off/On
M70 bit 2
-
-
0/1 = Off/On
M14 bit 8
0/1 = Off/On
M14 bit 9
0/1 = Off/On
M14 bit 10
0/1 = Local/remote
0/1 = Off/On
Defined by E20
0/1 = Off/On
Defined by E21
0/1 = Off/On
Defined by E22
0/1 = Off/On
Defined by E23
0/1 = Off/On
Defined by E24
0/1 = Off/On
Defined by E25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Frenic-hvac series