Fuji Electric FRENIC-AQUA series User Manual page 71

Rs-485 communication
Hide thumbs Also See for FRENIC-AQUA series:
Table of Contents

Advertisement

2) Communications dedicated function codes
Command data:
Monitor data 1:
Monitor data 2:
Alarm data 1:
Alarm data 2:
and others
For further information about these codes, see Chapter 5 "Function Codes and Data Formats."
Byte
Field
0
SOH
SOH
1
Station
0 to 3
address
2
0 to 9
3
ACK
ACK
4
Command
R
W
A
E
5
Function code
group *1
6
Function code
0 to 9
identification
number *1
7
0 to 9
8
Special
SP
additional
-
data
9
Data
0 to 9,
A to F
10
11
12
13
ETX
ETX
14
BCC
0 to 9,
A to F
15
*1 A space (SP = 20
S code
M code
W code
X code
Z code
Table 4.3 ACK frame
Value
ASCII
Hexadecimal
format
format
01
H
30
to 33
H
H
30
to 39
H
H
06
H
52
H
57
H
41
H
45
H
30
to 39
H
H
30
to 39
H
H
20
H
2D
H
30
to 39
H
H
41
to 46
H
H
03
H
30
to 39
H
H
41
to 46
H
H
) will be set for an alarm reset command.
H
4-4
Description
Start of message
Station address of the inverter (decimal: ten's figure)
Station address of the inverter (decimal: one's figure)
Transmission response
Acknowledgement: There was no receiving or logical
error.
Answerback of request command
Polling (read)
Selecting (write)
High-speed response selecting (write)
Alarm reset
See Table 4.4-1.
Function code identification number (decimal: ten's
figure)
Function code identification number (decimal: one's
figure)
Fixed to "sp (space)" normally.
"-" for negative data
Data's first character (hexadecimal: thousand's figure)
Data's second character (hexadecimal: hundred's
figure)
Data's third character (hexadecimal: ten's figure)
Data's fourth character (hexadecimal: one's figure)
End of message
Checksum 1 (hexadecimal: ten's figure)
Checksum 2 (hexadecimal: one's figure)