[ 3 ] Operation command data
Table 5.4 Function codes for operation command data
Code
Name
S06
Operation
Operation command via
command
communications
(general-purpose input
terminal functions (X1 −
X7, XF (FWD), XR
(REV)) and
communications
dedicated command
(FWD, REV, RST)
S14
Alarm reset
Alarm reset command
command
via communications
1) To make alarm resetting with S06, bit 15 must be set to 1 and then set back to 0. Alarm
resetting is impossible unless the communications side is made valid by the settings of
function codes H30, y98, and y99 and the "LE" assigned terminal.
2) S14 does not require the operation described in 1) above, and writing 1 permits alarm
resetting (because writing the value once turns ON the reset command that will be turned
OFF after a specific period of time). This command is 0 whenever it is read, and is always
valid, irrespective of function codes H30, y98, and y99 and the status of the "LE" assigned
terminal.
3) X1 to X7, XF (FWD), and XR (REV) operate according to the functions specified with
function codes E01 to E07, E98, and E99.
4) When giving operation command S06 via communications, the relation between S06 and the
inverter terminal (external signal input) command is shown in Table 5.4 on the next page.
The "Support" column of the table indicates whether each function is supported by the
respective models or not.
is not supported.
If alarm resetting is performed with the operation command (S06) uncleared, the inverter will
start to operate just upon alarm resetting. Before alarm resetting, confirm that the operation
command is cleared.
Otherwise, an accident may result.
5.1 Communications Dedicated Function Codes
Function
Permissible setting range
0000
* Legends in R/W column...R: Readable, W: Writable, R/W: Readable/writable
indicates the function is supported, and × indicates the function
5-5
Min. step
to FFFF
1
H
H
0 or 1
1
Unit
R/W *
R/W