Fuji Electric FRENIC-AQUA series User Manual page 49

Rs-485 communication
Hide thumbs Also See for FRENIC-AQUA series:
Table of Contents

Advertisement

[ 5 ] Read coil status
Query
1 byte
1 byte
Station
01
Coil address
H
address
Hi
Normal response
1 byte
1 byte
Station
01
H
address
How to set a query
-
Broadcast with station address 0 is not usable. If this address is used, no response is
returned.
-
'FC'=1 (01
)
H
-
Read out a coil (bit data) by specifying the top address of the coil to be read out and the
number of points read out (number of coils).
-
For the assignment of a coil (bit data), see Table 3.3. For each content, refer to the S and M
codes in the remarks column.
Coil
+7
+6
number
1
X6
X5
9
RST
XR
17
VL
TL
25
BUSY
33
FAN
KP
41
49
X6
X5
57
RST
XR
65
73
-
The "−" symbols in the table mean that the bit is reserved and always zero.
-
Coil addresses are 0 to 79, calculated by subtracting one from coil numbers. If a coil address
is 80 or more, an error occurs because of an incorrect address.
-
The number of coils is 1 to 80. If the number of coils exceeds the range, an error occurs
because of an incorrect address.
-
No error occurs even if the sum of the numbers of coil addresses and coils exceeds the coil
range.
2 bytes
2 bytes
No. of coils
Lo
Hi
1 byte
1 to 10 bytes
Byte count
Read data
Table 3.3 Description of coil (bit data)
+5
+4
+3
X4
X3
X2
XF
NUV
BRK
INT
WR
RL
ALM
OL
IPF
SWM2
IDL
ID
OPL
X4
X3
X2
XF
Y5
Y4
3-8
2 bytes
Error check
Lo
2 bytes
Error check
+2
+1
+0
X1
REV
FWD
X7
EXT
REV
FWD
DEC
ACC
IL
RDY
FDT
FAR
LIFE
OH
TRY
X1
REV
FWD
X7
Y3
Y2
Y1
30
Remarks
S06: Run operation
command
(Read/Write)
M14: Run status
(Read only)
M70: Run status 2
(Read only)
M13: Run operation
command (final
command)
(Read only)
M15: General-purpose
output terminal
information
(Read only)