Fuji Electric FRENIC-AQUA series User Manual page 159

Rs-485 communication
Hide thumbs Also See for FRENIC-AQUA series:
Table of Contents

Advertisement

Data format [40]
Alarm factor
15
14
13
12
Alarm caused by
multiple factors (1 to 5)
Data format [41]
Alarm history
15
14
13
12
Number of serial occurrences of same alarm
Indicates the content of an alarm that has occurred and the number of serial occurrence
times of the alarm.
Data format [43]
Operation command (for I/O check)
15
14
13
12
0
0
0
0
Unused
(All bits are turned ON when set to 1.)
Data format [44]
Operation status 2
15
14
13
12
0
0
IDL
ID
(All bits are turned ON or become active when set to 1.)
Bit Symbol
Description
0
FAR
Frequency arrival
signal
1
FDT
Frequency level
detection
2
RDY
Inverter ready to
run
3
SWM2 2nd motor is
selected
4
IPF
Auto-restarting
after recovery of
power
5
OL
Motor overload
early warning
6
KP
Running per
keypad
7
FAN
Cooling fan in
operation
*1 The "Support" column indicates whether each inverter type supports the corresponding bit or not.
The symbol "O" means the code is supported and the symbol "X" means that the code is not
supported (fixed to 0).
11
10
9
8
Order of alarm
occurrences (1 to 5)
11
10
9
8
11
10
9
8
0
0
0
X7
X6
General-purpose input
11
10
9
8
OLP
LIFE OH TRY FAN KP
Support
HVAC
AQUA
×
×
×
×
5-72
7
6
5
4
Alarm code (See Table 5.32.)
7
6
5
4
Alarm code (See Table 5.32.)
7
6
5
4
X5
X4
X3
X2
7
6
5
4
OL
IPF
Bit Symbol
Description
8
TRY
Retry in operation
9
OH
Heat sink overheat
early warning
10
LIFE
Lifetime alarm
11
OLP
Overload
prevention control
12
ID
Current detection
13
IDL
Low level current
detection
14
ID2
Current detection 2
15
0
3
2
1
0
3
2
1
0
3
2
1
0
X1
REV
FWD
General-
purpose input
3
2
1
0
0
RDY
FDT
FAR
Support
HVAC
AQUA
×
×
×
×
×
×

Advertisement

Table of Contents
loading

This manual is also suitable for:

Frenic-hvac series