To Connect The Jlg Control System Analyzer To The Generator; Alarms And Fault Flash Codes - JLG E600 Service And Maintenance Manual

Hide thumbs Also See for E600:
Table of Contents

Advertisement

To Connect the JLG Control System Analyzer
to the Generator
The JLG Control System Analyzer can be used to monitor
generator settings and conditions. Connect the analyzer
as follows:
1. Connect the four pin end of the cable supplied with
the analyzer, to the connector behind the ground
control module located on the left side of the
machine next to the ground control station and con-
nect the remaining end of the cable to the analyzer.
The ground control module contains the settings for
the generator.
NOTE: The cable has a four pin connector at each end of
the cable; the cable cannot be connected back-
wards.
2. Power up the Analyzer by pulling out the ground sta-
tion EMS and positioning the Generator Enable
switch on the platform control box to the "on" posi-
tion. Refer to Figure 3-34., Generator System Ana-
lyzer Flow Chart
3121813
SECTION 3 - CHASSIS & TURNTABLE

Alarms and Fault Flash Codes

In the event of an RBS alarm, a flash code will be issued
and an alarm indicated on the analyzer.
NOTE: Alarms must be reset once the fault has been cor-
rected.
Table 3-6. Generator System Flash Codes
Code
Alarm
1-1
Low Oil Pressure
1-2
High Engine Tem-
perature
1-3
Engine Overspeed
1-4
E n g i n e
speed/Overcrank
1-5
No Speed Signal
2-1
Overvoltage
2-2
E n g i n e S t a r t i n g
System fault
2-3
Not Used
2-4
L o s s o f Vo l t a g e
Sense
Unit Disabled
Contin-
uous
Off
Unit Disabled
• Low Oil Pressure
Enabled once TDBP (time delay bypass) period has
elapsed after engine startup. If the low engine oil pressure
switch closes, the engine will stop immediately and a low
oil pressure alarm will be indicated.
• High Engine Temperature
If the engine oil temperature exceeds the high engine tem-
perature setting, the engine will stop immediately and a
low oil pressure alarm will be indicated.
• Overspeed
If the engine speed exceeds the overspeed limit, the
engine will stop immediately and an overspeed alarm will
be indicated.
– JLG Lift –
Description
Shutdown due to low engine
oil pressure
Shutdown due to high engine
oil temperature
Shutdown due to high engine
speed
U n d e r-
S h u t d o w n d u e t o e n g i n e
overcrank or underspeed
S h u t d o w n d u e t o l o s s o f
speed signal
Shutdown due to high output
voltage
Alarm not a shutdown; Indi-
c a t e s p r o b l e m w i t h t h e
engine starting system
Not Used
Shutdown due to loss of volt-
age sensing
No Faults. RBS enabled and
can respond to any CTS
RBS off or disabled; Will not
respond to any CTS