RBS Start

Call to start
Manual
Automatic
Engine start time
delay
Preheat delay
Crank time
(Rest time)
Time delay bypass
3-66
48V DC applied to the input
1 Low battery voltage (below
48VDC)
2 Low engine temperature
(below 5°C)
3 Low start battery voltage
(below 12.2V)
RBS waits to verify that call to
start is valid (not a transient con-
dition).
- if engine temperature is below
32°F (0°C)
RBS will crank and rest until
engine starts, or Overcrank fault
is indicated after 3 failed crank
cycles.
RBS waits until normal engine
operating conditions are
reached before Low oil pressure
and Underspeed faults are moni-
tored.
– JLG Lift –

RBS shutdown

Call to start removed
Manually
Automati-
cally:
Engine run time delay
Cool-down period
Inhibit run input applied
1 Battery voltage above
54VDC and finish charging cur-
rent below 30ADC
2 Engine temperature above
8°C
3 Start battery voltage above
12.9V and finish charging cur-
rent below 30ADC
This period ensures that no fur-
ther call to start conditions
occur prior to cool-down period.
Alternator output is reduced to a
minimal level to allow the engine
to cool down.