SECTION 6 - JLG CONTROL SYSTEM
6.2 TO CONNECT THE JLG CONTROL SYSTEM
ANALYZER
1. Connect the cable supplied with the analyzer, to the
controller module in the ground control box and con-
nect the remaining end of the cable to the analyzer.
NOTE: The cable has a four pin connector at each end of the cable;
the cable cannot be connected backwards.
2. Power up the Control System by turning the key to the
ground position and pulling the emergency stop button
on.
6-2

Using the Analyzer

With the machine power on and the analyzer connected prop-
erly, the analyzer will display the following:
MENU:
HELP: PRESS ENTER
ESC
MENU:
HELP:PRESS ENTER
Move between top level menu items using
RIGHT
and LEFT
played menu item, press ENTER
menu item, press ESC
using the right and left arrow keys to select a different menu
item.
The top level menus are as follows:
HELP
DIAGNOSTICS
SYSTEM TEST
ACCESS LEVEL
PERSONALITIES
MACHINE SETUP
CALIBRATIONS (view only)
ENTER
MAE19060
arrow keys. To select a dis-
. To cancel a selected
then you will be able to scroll
3121200