Enclosure Data

Input
1
HP
Volts
0.5
E7U22P21
0.75
E7U22P21
1
E7U22P21
2
E7U22P21
3
E7U22P21
5
E7U23P71
208
7.5
E7U27P51
10
E7U27P51
15
E7U20111
20
E7U20151
25
E7U20181
Note 1: Horsepower rating is based on a standard NEMA B 4-pole motor.
Note 2: The underscore position in these model numbers codes for the enclosure type: V = NEMA1, B = NEMA12 FVFF.
Note 3: Heat loss is the amount of heat dissipated by the drive at full load with all standard options available inside the enclosure. Drive heat sink losses are
included in the heat loss data.
Note 4: Height dimension (H) excludes the mounting screw tabs. Depth dimension (D) excludes the disconnect handle.
Note 5: This data represents the total weight with all possible standard options. Weight could be less depending on the options specified.
Note 6: All standard options are available in this size enclosure.
Table 1.2 208V Enclosure Data
Drive
2
Bypass
Model
Model
CIMR-
Number
E7L_D002
E7L_D003
E7L_D004
E7L_D007
E7L_D010
E7L_D016
E7L_D024
E7L_D030
E7L_D046
E7L_D059
E7L_D074
OL
3
Heat
NEC
110%
Loss
FLA
1 min
Watts
2.4
2.6
68
3.5
3.8
68
4.6
5.1
78
7.5
8.2
110
10.6
11.7
141
16.7
18.4
202
24.2
26.6
273
30.8
33.9
365
46.2
50.8
578
59.4
65.3
653
74.8
82.3
746
Physical Installation 1 - 3
4
Enclosure Dimensions
NEMA 1 & NEMA 12 -FVFF
H
W
D
inches
29.48
19.06
13.66
6
Dimension Drawing
S-5537
40.48
25.63
14.66
6
Dimension Drawing
S-5539
5
Weight
Electrical