YASKAWA E7LVD002 Technical Manual page 63

Drive/bypass
Table of Contents

Advertisement

Bypass Motor OL Indicator
Indicator Status
On (Red)
Safeties Open Status Indicator
Indicator Status
On (Red)
Drive Fault Indicator
Indicator Status
On (Red)
Smoke Purge Status Indicator
Indicator Status
On (Amber)
Table 3.9 Motor OL Indicator
The motor overload (S10 on schematic E7L-00) has tripped OFF de-
energizing both the Drive and Bypass Circuits.
Off
The motor overload (S10) is satisfied.
Table 3.10 Safeties Open Indicator
The NC "motor safety circuit" connected to terminals TB1-1 and TB1-9
has an open circuit condition.
Off
The NC "motor safety circuit" is satisfied or this function is disabled by
DIP switch S2-7.
Table 3.11 Drive Fault Indicator
The Drive has tripped OFF due to an internal Drive fault.
Off
The Drive is ready for operation, or operating normally.
Table 3.12 Smoke Purge Indicator
The Smoke Purge function has been activated, the building fire control
system has closed a contact between terminals TB1-5 and TB1-9.
Off
Smoke Purge is not active, the Drive & Bypass are operating normally.
Description
Description
Description
Description
Control Panel 3 - 7