YASKAWA E7LVD002 Technical Manual page 283

Drive/bypass
Table of Contents

Advertisement

Table E.2 Recommended Fuse and Circuit Breaker Ratings per NEC (480Vac Input)
Model
Hp
CIMR-E7U
40P4
0.5/0.75
40P7
1
41P5
1.5/2
42P2
3
43P7
5
44P0
-
45P5
7.5
47P5
10
4011
15
4011
20
4015
25
4018
30
4022
-
4030
40
4030
50
4037
60
4045
75
4055
100
4075
125
4090
150
4110
200
4132
-
4160
250
4185
300/350
4220
400/450
4300
500+
*1 Input and Output Amps are based on the Normal Duty (ND) current rating. Consult the Specification section for details on the Heavy Duty (HD) and Normal Duty (ND) ratings.
Input
Output
Amps
Amps
*1
*1
(Continuous
(Continuous
Rating)
Rating)
2.2
1.8
2.5
2.1
4.4
3.7
6.4
5.3
9
7.6
10.4
8.7
15
12.5
20
17
33
27
33
27
40
34
48
40
55
50.4
74
67.2
74
67.2
85
77
106
96
134
125
172
156
198
180
264
240
286
260
334
304
456
414
567
515
743
675
Peripheral Devices E - 3
Fuse
Selection Criteria
Maximum
Maximum
Time-Delay
Non-Time-Delay
Fuse Rating (A)
Fuse Rating (A)
4
4
8
10
15
15
25
30
45
45
60
70
80
100
100
125
150
200
250
300
350
400
450
600
700
900
Circuit Breaker
Selection Criteria
Maximum CB
Rating (A)
10
10
12
15
20
30
30
30
50
50
70
80
80
100
100
125
150
200
250
300
350
400
450
600
700
1000
900
1200
15
15
15
15
20
20
30
40
60
60
80
90
100
125
125
150
200
225
300
400
450
600
700
800

Advertisement

Table of Contents
loading

Table of Contents