When the output frequency has dropped below the DC Injection Start Frequency in b2-01 (Default = 0.5HZ) DC current will be
injected in the motor at a level determined by b2-02 (50% Default). The DC Injection condition will occur for the time
specified by b2-04 (0.0 Default), to establish the end point of the ramp. DC injection can be used to insure the motor is at zero
rpm prior to the Drive shutting off.
Run Command
Output Frequency
The actual deceleration time can be determined by the following formula
Output
Freq.
=
Time
to
Stop
Maximum
If S-Curve characteristics are specified by the Drive programming, they will add to the total time to stop.
1:Coast to stop: When the Run command is removed, the Drive will turn off its output and the motor will coast (uncontrolled
deceleration). The friction of the driven equipment will eventually overcome any residual inertia of the sys-
tem and the rotation will stop.
Run Command
Output Frequency
After a stop is initiated, a subsequent Run commands input before the Minimum Baseblock Time (L2-03)
IMPORTANT
has expired, will be ignored.
100 %
Deceleration Time (C1-02)
0 %
Fig 5.2
at time
of
stop
command
Frequency
(E1
-
04)
100 %
0 %
Fig 5.3 Coast to Stop
Programming 5 - 14
TIME
Deceleration to Stop
×
Setting
of
active
Decel
Time
Motor Speed
Drive Output Frequency Interrupted
TIME
(CLOSED)
ON
(OPEN)
OFF
b2-01
DC Injection Brake
|
b2-04
|
02 or C1-04)
(C1
-
02)
(CLOSED)
ON
OFF
(OPEN)