YASKAWA E7LVD002 Technical Manual page 150

Drive/bypass
Table of Contents

Advertisement

H3-10 Drive Terminal A2 Gain Setting
Setting Range:
0.0 to 1000.0%
Factory Default: 100.0%
H3-11 Drive Terminal A2 Bias Setting
Setting Range:
-100.0% to +100.0%
Factory Default: 0.0%
Parameters H3-10 and H3-11 perform the same function for the A2 analog input that parameters H3-02 and H3-03 perform for
the A1 analog input. Please refer to the parameter description for H3-02 and H3-03 for information about H3-10 and
H3-11.
These parameters could be used for final calibration of a factory or field installed pressure to electric transducer input
connected to terminal A2 and AC. This field calibration may be needed if there is a job site variation from the typical 3 to 15
PSIG pneumatic signal input range.
H3-12 Analog Input Filter Time Constant
Setting Range:
0.0 to 2.00 Seconds
Factory Default: 0.30 Seconds
An analog input filter can be used to prevent erratic Drive control when a "noisy" analog reference is used. Parameter H3-12
sets the time constant for a first order filter that will be applied to both the A1 and A2 analog inputs. The Drive operation
becomes more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.
Noisy
input
signal
Fig 5.29 Analog Input Filter Time Constant Effect on "Noisy" Signal
Programming 5 - 58
Analog
Input
Filter
Internal Analog Input Valve
Analog
(Filtered)
input post