YASKAWA E7LVD002 Technical Manual page 103

Drive/bypass
Table of Contents

Advertisement

If A1-01 is configured for Advanced Access (A1-01= "2: Advanced Level"), then all menus and all parameters are shown. If the
Access Level Selection is set to Advanced, all parameters should be adjustable unless:
1. The Drive parameters are password protected (A1-04) which will prevent access to A1-00 through A1-03 and all A2
parameters.
2. A digital input has been configured as a Program Lockout (H1-0X= 1B) is active.
3. During serial communication writing, if a parameter change is also attempted via the digital operator, a
"BUSY - WRITE PROTECTED" message will display. Parameter change will not be possible from the digital operator until an
Enter command is received via the serial communication to finish the serial writing process.
A1-03 Initialize Parameters
Setting
0
No Initialize (factory default)
1110
User Initialize
2220
2-Wire Initialize
3330
3-Wire Initialize
The Drive can be set back to one of three default states via the A1-03 parameter.
Note: The E7L application of the Drive employs "2-wire" control.
1. User Initialization – 1110:The modified Drive parameters are returned to the values selected as user settings. User settings
2. 2-Wire Initialization – 2220: The Drive parameters are returned to factory default values with digital inputs S1 and S2
3. 3-Wire Initialization – 3330: The Drive parameters are returned to factory default values with digital inputs S1, S2, and S5
After an initialization is performed, parameter A1-03 will automatically be set back to 0.
S1
FWD Run/Stop
S2
REV Run/Stop
SN
2-wire control
2-wire control
See "Virtual Terminals" note on page 5-2.
Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The following parameters will
IMPORTANT
not be reset when parameter A1-03=2220 or 3330:
Description
are stored when parameter o2-03= "1: Set Defaults".
configured as Forward Run and Reverse Run, respectively.
configured as Run, Stop, and Forward/Reverse respectively.
Fig 5.1 2 & 3-Wire Control Wiring Examples
A1-00
Language Selection
E1-03
V/f Pattern Selection
o2-04
kVA Selection
o2-09
Initialization Specification Selection
Programming 5 - 11
Stop
Operation
switch
switch
(NC contact)
(NO contact)
S3 or S5
3-wire control
Run command
(run on momentary close)
Stop command
(stop on momentary open)
Forward/reverse command
SN
(multi-function input)
Sequence input common

Advertisement

Table of Contents
loading

Table of Contents