Metasys N2 Analog Output (AO) Summary
Object ID
AO 1
AO 2
AO 3
AO 4
AO 5
AO 6
STALL PREVENTION LEVEL – RUN
AO 7
STALL PREVENTION LEVEL – ACCEL
AO 8
REFERENCE OPERATION MODE SELECT
AO 9
RUN OPERATION MODE SELECT
AO 10
AO 11
FREQUENCY COMMAND UPPER LIMIT
AO 12
FREQUENCY COMMAND LOWER LIMIT
AO 13
AO 14
AO 15
AO 16
AO 17
JUMP FREQUENCY BANDWIDTH
AO 18
NUMBER OF AUTO RESTARTS
AO 19
OPERATOR DISPLAY MODE
AO 20
POWER LOSS RIDE THROUGH
AO 21
AO 22
AO 23
AO 24
AO 25
AO 26
AO 27
MISSING DETECTION SELECT
AO 28
MISSING DETECTION LEVEL
AO 29
MISSING DETECTION TIME
AO 30
READ PARAMETER NUMBER
AO 31
WRITE PARAMETER NUMBER
AO 32
Table D.10 Metasys N2 Analog Output Summary (Metasys N2 to E7)
Object Name
SPEED COMMAND
ACCELERATION TIME
DECELERATION TIME
PI PROPORTIONAL GAIN
PI INTEGRAL TIME
PI MODE SELECT
MOTOR RATED CURRENT
JUMP FREQUENCY 1
JUMP FREQUENCY 2
JUMP FREQUENCY 3
CABLE LOSS TIME-OUT
CABLE LOSS SPEED
PI INTEGRAL LIMIT
PI UPPER LIMIT VALUE
PI OFFSET ADJUSTMENT
PI PRIMARY DELAY TIME
PI FEEDBACK REFERENCE
PI FEEDBACK REFERENCE
PI FEEDBACK REFERENCE
WRITE PARAMETER DATA
Communications D - 17
Units
Default Value
0.01 Hz
SEC
30.0
SEC
30.0
-
2.00
SEC
5.0
%
120
%
120
-
1
-
1
-
0
% of MAX
100.0
% of MAX
0.0
A
Motor model dependent
0.1Hz
0.0
0.1Hz
0.0
0.1Hz
0.0
0.1Hz
1.0
-
0
-
0
SEC
Drive model dependent
SEC
2.0
0.01Hz
0.00
0.1%
100.0
0.1
100.0
0.1
0.0
0.01
0.00
1
0
1%
0
0.1 SEC
1.0
-
-
-
E7 Parameter
-
C1-01
C1-02
b5-02
b5-03
L3-06
L3-02
b1-01
b1-02
b5-01
d2-01
d2-02
E2-01
d3-01
d3-02
d3-03
d3-04
L5-01
o1-03
L2-02
H5-09
d1-04
b5-04
b5-06
b5-07
b5-08
b5-12
b5-13
b5-14
-
-
-