YASKAWA E7LVD002 Technical Manual page 144

Drive/bypass
Table of Contents

Advertisement

Option/Inv Function Input Status
To switch the command source between the serial communication port and the control circuit terminals be sure to program the
following parameters:
Set b1-01 (Frequency Reference Selection) to 1 (Terminals).
Set b1-02 (Run Command Selection) to 1 (Terminals).
Set H1-0x (Input Terminal Function Selection) to 6B or 6C.
The Com/Inv Sel 2 function will operate the same way except the logic is reversed. When a digital input is programmed for the
Com/Inv Selection function (H1-0x= 6C) that input will function as follows:
Option/Inv Function Input Status
IMPORTANT
OPEN
CLOSED
OPEN
CLOSED
Switching the Reference and Run sources can only be done while the Drive is stopped.
Programming 5 - 52
Table 5.12
Run and Speed Command Source
From the control circuit and analog input terminals
From Serial Com port (R+,R-,S+, and S-) (embedded protocols)
Table 5.13
Run and Speed Command Source
From Serial Com port (R+, R-, S+, and S-) (embedded protocols)
From the control circuit and analog input terminals