YASKAWA E7LVD002 Technical Manual page 164

Drive/bypass
Table of Contents

Advertisement

o1-02 Power-On Monitor
Setting
1
Frequency Reference (factory default)
2
Output Frequency
3
Output Current
4
User Monitor (set by o1-01)
When the Drive is powered up, the display monitor is the "Power-On" monitor. The factory default "Power-On monitor" is
Speed Command (U1-01). Pressing the INCREASE key once scrolls the monitors to show the next two sequential monitors,
Output Frequency (U1-02), Output Current (U1-03) and User Monitor as selected by o1-01. The factory default for o1-01 is the
Output Voltage, monitor (U1-06).
The active monitor displayed when the Drive is powered on can be changed to either be U1-01 (Speed Command), U1-02
(Output Frequency), U1-03 (Output Current), or the User Monitor.
For example, if the Drive needs to display the Elapsed Timer as the Power-On monitor, then o1-01 must be set to "13" and
o1-02 must be set to "4". The next time Drive power is cycled, the digital operator displays U1-13 (Elapsed Time).
Description
Programming 5 - 72