YASKAWA E7LVD002 Technical Manual page 230

Drive/bypass
Table of Contents

Advertisement

Parameter
Parameter Name
No.
LCD Digital Operator Display
H4-06
Terminal AM Bias Setting
Terminal AM Bias
Terminal FM Signal Level
H4-07
Selection
AO Level Select1
Terminal AM Signal Level
H4-08
Selection
AO Level Select2
Drive Node Address
H5-01
Serial Comm Adr
Communication Speed Selection
H5-02
Serial Baud Rate
Communication Parity Selection
H5-03
Serial Com Sel
Stopping Method after
H5-04
Communication Error
Serial Fault Sel
Communication Error Detection
H5-05
Selection
Serial Flt Dtct
Drive Transmit Wait Time
H5-06
Transmit WaitTIM
RTS Control Selection
H5-07
RTS Control Sel
Communication Protocol
H5-08
Selection
Protocol Select
Communication Error
H5-09
Detection Time
CE Detect Time
Denotes that parameter can be changed when the drive is running.
* After these parameters are changed, drive power must be cycled before the changes will take effect.
# Hex, see page A-30.
Table A.1 Parameter List (Continued
Description
Analog Outputs
Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 0% output.
0: 0 - 10 VDC
2: 4-20 mA*
0: 0 - 10 VDC
2: 4-20 mA*
* An analog output of 4 - 20 mA can not be used with
the standard terminal board. Therefore an optional
terminal board (with shunt connector CN15) is needed.
Serial Com Setup
Selects drive station node number (address) for
terminals R+, R-, S+, S-.*
An address of "0" disables serial com.
Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
Selects the communication parity for terminals R+, R-,
S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity
Selects the stopping method when a communication
error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Run at d1-04 - available when H5-08=
"1: N2 METASYS" or "2: FLN APOGEE"
Enables or disables the communications timeout
detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than
the time specified in parameter H5-09,
a communications fault will occur.
Sets the time from when the drive receives data to when
the drive sends data.
Enables or disables "request to send" (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
Selects the communication protocol.
0: Memobus (Modbus)
1: N2 (Metasys)
2: FLN (APOGEE)
Determines how long communications must be lost
before a fault is annunciated. Works in conjunction with
parameters H5-05 and H5-04.
Parameters A - 18
)
Setting
Factory
Range
Setting
–110.0 to
0.0%
110.0
0 or 2
0
0 or 2
0
0 to 20
(H5-08=0)
0 to FF
1F #
(H5-08=1)
0 to 63
(H5-08=2)
0 to 4
3
0 to 2
0
0 to 3
3
0 or 1
1
5 to 65
5ms
0 or 1
1
0 to 2
0
0 to 10.0
(H5-08=0)
0 to 10.0
2.0sec
(H5-08=1)
0 to 90.0
(H5-08=2)
Menu
Location
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming
Programming

Advertisement

Table of Contents
loading

Table of Contents