YASKAWA E7LVD002 Technical Manual page 117

Drive/bypass
Table of Contents

Advertisement

Parameters Effected by Options Specified and
Settings
Options
Specified
H1-03
H1-04
b5-01
H3-08 H5-2 H5-7 H5-8
(S5)
(S6)
PI Control
1
19
@
PI Control
1
19
@
J & PI
1
6C
19~
U & PI
1
6C
19~
V & PI
1
6C
19~
L & PI
1
6C
19~
Definitions:
L = LonWorks Option Card
J = Native Protocol, Metasys N2
P = Pneumatic Interface (3 to 15 PSIG)
U = Native Protocol, APOGEE FLN
V = Native Protocol, Modbus
Parameter Reference:
b5-01:
PI Control Selection
0: Disable (default)
1: Enable
H1-03:
Drive Terminal S5 Function Selection
3: Multi-step Ref 1 (default)
6C: Com/Inv Sel 2
H1-04:
Drive Terminal S6 Function Selection
4: Multi-step Ref 2 (default)
19: PI Disable
H3-08:
Drive Terminal A2 Signal Level
0: 0 - 10 VDC
2: 4 - 20 mA (default)
DIP Switch Reference:
S1-1:
Terminating resistor, always on for option L, otherwise on only if last device.
S1-2:
Drive Terminal A2 signal level
On = 4-20 mA
S4-2:
Drive input terminal S4 operation
On = Input S4 operates inversely with input S5
Off = Inputs S4 and S5 operate independently
Notes:
Hand mode run/stop for Drive and Bypass is always via the front control panel HAND selector key.
Auto mode run/stop for Drive and Bypass without serial com. is from terminal TB1-2.
Auto mode run/stop with serial com. is from serial com. for both Drive and Bypass modes.
DIP switch configurable terminal TB3-3 is connected to Drive terminal A2 (the default). See Chapter 2 Table 2.8 for the alternate TB3-3 configuration.
A Jumper is required from TB5-2 to TB5-7. This is essential for serial com. applications and benign for all other applications.
Table 5.4 Option Dependent Bypass Parameter Settings with PI Control
PCB DIP
Switch S1
1
2
2
@
@
@
@
On
0
@
@
@
@
Off
0
3
1
1
Off Off
0
2
1
2
Off Off
0
3
1
0
Off Off
0
3
0
0
On
Off
Off = 0-10 VDC
HAND Speed
Drive Terminal A2
Command
Signal Level via TB3-3
Source
PCB DIP
Switch S4
2
Keypad
4-20
d1-01
mA
Off
X
X
Off
X
Off
X
Off
X
Off
X
Off
X
* = The Drive factory default
# = The H/O/A selector keys must have AUTO selected
to allow serial com. to control the Drive
@ = Don't care
~ = Jumper required TB5-5 to TB1-12 and TB1-13 to TB5-2
H5-02:
Communication Speed Selection
3: 9600 Baud (default)
2: 4800 Baud
H5-07:
RTS Control Selection
0: Disabled (RTS always on)
1: Enabled (RTS on only when sending) (default)
H5-08:
Communication Protocol Selection
0: Modbus (default)
1: N2 (Metasys)
2: FLN (APOGEE)
d1-01:
Frequency Reference 1
Programming 5 - 25
or TB5-9
Run/Stop
0-10
3-15
VDC
PSIG
Terminal
Serial
TB1-2
#
X
X
X
X
X
X
X
X
X
X
X
AUTO
Speed or
Setpoint
Feedback
TB3-3
Serial
Serial
Keypad
(A2)
#
#
X
X
X
X
X
X
X
X
X
X
X
X