YASKAWA E7LVD002 Technical Manual page 116

Drive/bypass
Table of Contents

Advertisement

SETTING
PARAMETER
Bypass & PI
NUMBER
Control
b1-01
0
b5-01
1
H1-03
SEE TABLE
5.4
H1-04
SEE TABLE
5.4
H3-08
SEE TABLE
5.4
H3-09
B
H5-02
SEE TABLE
5.4
H5-07
SEE TABLE
5.4
H5-08
SEE TABLE
5.4
Table 5.3 PI Control Parameter Settings in E7L Bypass Units
Bypass
UNITS
Default
SEE TABLE
N/A
Frequency Reference Selection – Selects the
5.2
speed command input source
0
N/A
PI Mode Selection – Enables PI mode
SEE TABLE
N/A
Drive Terminal S5 Function Selection – Set
5.2
for various operating modes
4
N/A
Drive Terminal S6 Function Selection – Set
for PI Disable, turn off PI controller
SEE TABLE
N/A
Drive Terminal A2 Signal Level – Signal
5.2
selection, 0 to 10 VDC (Drive control board
switch S1-2 off) or 4 to 20 mA (Drive con-
trol board switch S1-2 on)
SEE TABLE
N/A
Drive Terminal A2 Function Selection –
5.2
Selects how this input will be used by the
Drive
3
N/A
Serial Communication Speed Selection,
Baud Rate
1
N/A
Serial Communication Request to Send
Control
0
N/A
Serial Communication Protocol Selection
Programming 5 - 24
DESCRIPTION
OPTIONAL LCD
KEYPAD DISPLAY
For Bypass Setting
Reference Source / Terminals
PI Mode Setting / PI Mode
Terminal S5 Sel / Com/Inv Sel 2,
for example
Terminal S6 Sel / PI Disable
Term A2 Signal / 0-10 VDC
Terminal A2 Sel / PI Feedback
Serial Baud Rate/
9600 Baud
RTS Control Sel/enabled
Protocol Select/N2 (Metasys)