socomec MASTERYS IP Plus Installation And Operating Manual page 38

10-40 kva
Table of Contents

Advertisement

8
MENU
PRESENT CONFIGURATIONS menu
A Parameter
• BATTERY RECHARGE
TEMP COMPENSATION
• BACKFEED TYPE
• BATTERY TEST
TEST EVERY XX DAYS
• LAN IP STATICO
XXX . XXX . XXX .XXX
• SERIAL LINK JBUS
SLAVE NUMBER
DATE AND TIME
• EXTENDED COMMAND
• REMOTE COMMAND
BUZZER
LCD CONTRAST
• STATISTICS PERIOD
• GSS TIME DELAY
E-SERVICE TYPE
E-SERVICE TELEPHONE
NUMBER
38
IOMMASIPXX09-GB 04
Description
Sets the recharge voltage compensation value
according to the battery temperature (not present
with external battery cabinets.
Sets the type of backfeed protection.
Sets the frequency rate of the battery test in days
(zero = do not perform the test).
Sets the static IP address of the LAN
Sets the mimic panel jbus node
Sets the date and time
Enables/Disables the mimic panel extended commands
Enables/disables the remote controls
Enables/Disables the buzzer
Sets the LCD display contrast
Indicates the time in weeks for the calculation of statistics
Sets the generator start up delay time (visible only when
the GSS PCB is installed)
Select e-service operating mode
Insert the phone number to call for e-service messages
MASTERYS IP+
Allowed values
YES/NO
DISABLE
BY-PASS-INPUT ALONE
BY-PASS-INPUT COMMON
0÷180
255.255.255.255
1÷15
DD/MM/YY HH:MM
YES/NO
YES/NO
YES/NO
0/100
1÷10
1÷60 MINUTES
NONE, MODEM, SMS
MAX 20 CHARACTERS
10-40 kVA