Technical Specifications - socomec MASTERYS IP Plus Installation And Operating Manual

10-40 kva
Table of Contents

Advertisement

11

TECHNICAL SPECIFICATIONS

Models
Input/Output phases
Electrical specifi cations - Input
Mains voltage
Input frequency
Input power factor
THDI
Electrical specifi cations - Output
Output voltage (three phase + neutral)
Frequency
Automatic bypass
Nominal power (kW)
Overload on automatic bypass @ 25 °C
Crest factor
Voltage distortion
(1) @ Pout = 90% Pnom.
(2) With transformer on output or bypass.
Environment
Operating temperature
Storage temperature
Relative humidity
Max. altitude
Acoustic noise (dB)
3
Required cooling capacity (m
/h)
Dissipated power max (W)
Dissipated power (BTU/h)
Standards
Safety (TÜV SÜD certifi ed)
Type and performance
EMC
Product certifi cation
Protection level
54
IOMMASIPXX09-GB 04
10
15
3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3
10
15
3P+N 400 V +20% -15% (up to -35% @70% of nominal load)
50-60 Hz ±10%
10
15
230 V single phase (selectable: 208
400 V three phase (selectable 360
50-60 Hz ±2% (from 1% to 8% if generator is used)
nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
9
13,5
(2)
20 minutes @ 125%, 4 minutes @ 150%, 2 minutes @ 200%
1% with linear load
10
15
0÷40 °C (15÷25 °C recommended for longer battery life)
0÷95% condensation-free
1.000 m (3.300 ft) without derating; 3.000 m (10.000 ft) max
< 52
< 52
280
280
680
900
2300
3050
10
15
EN 62040-1-1, EN 60950-1
EN 62040-3 (VFI-SS-111)
EN 62040-2
CE, TÜV SÜD
MASTERYS IP+
20
30
40
3/3
20
30
40
0,99
< 2.5%
20
30
40
(1)
/220/230/240 V) ±1%
(1)
/380/400/415 V) ±1%
18
27
36
3:1
20
30
40
-5÷45 °C
< 52
< 55
< 55
280
465
465
1150
1750
2300
4070
6050
7900
20
30
40
IP31
10-40 kVA
800
600
Weight: up to 500 kg
WEIGHT