Commissioning

6.7 Adding device to communication network

6.7
Adding device to communication network
Before setting the parameters, it is necessary to configure the FC410 project in PDM.
1. Add the device to SIMATIC Modbus network:
– Select File → New
– Go to View and select Process Device Network view.
– Right-click on the typed in
– Right-click on Networks and Insert New Object → Communication Network.
– Click on Assign Device Type and select Modbus Network.
– Right-click Modbus Network and select Insert New Object → Object.
– Click on Assign Device Type, and select Devices → Modbus → Sensors → Flow →
2. Set up the communication parameters for SIMATIC Modbus network:
– Select Networks → My computer, right-click on COM Port Interface and select Object
– Select the Communication tab and configure the communication parameters. FC410
54
Type in a project name, for example
Click OK two times. Your PC is now added to the Modbus Network.
Coriolis → SIEMENS AG → SITRANS FC410
Click OK two times.
Image 6-1
Assigning Modbus device to network
Properties.
default settings are:
- Transmission rate: 19200 baud
- Parity: even
FC410 commissioning
Project name
and select Insert New Object → Networks.
Operating Instructions, 02/2016, A5E33120874-AC
.