Advertisement

Connecting
5.4 Connecting the FC410
5.4.2

Cable termination version

A: Prepare the cable by stripping it at both ends.
Image 5-1
B: Connect wires within the sensor terminal compartment
1. Remove the lock screw and remove the lid.
2. Undo the flexible strap.
3. Disconnect the sensor connection (white plug) from the electronic.
4. Loosen the mounting screw using a TX10 Torx driver and remove the electronic from the
housing.
5. Remove the cap and the ferrule from the cable gland and slide onto the cable.
6. Push the cable through the open gland and anchor the cable shield and the wires with the
clamp bar.
7. Remove the terminal block from the electronic.
8. Connect the wires to the terminals according to the list below.
40
Cable end
Terminal number
1
2
3
4
Description
24 VDC
0 VDC
B
A
Operating Instructions, 02/2016, A5E33120874-AC
Wire color (Siemens cable)
Orange
Yellow
White
Blue
FC410 with Modbus