Installing The Device Driver; Adding The Device To The Network; Configuring The Device - Siemens SITRANS FUS080 Operating Instructions Manual

Ultrasonic flowmeters
Table of Contents

Advertisement

Commissioning
6.4 Commissioning via PDM
6.4.2

Installing the device driver

Install the PDM device driver as follows:
1. Download update from the Internet on SITRANS F US downloads
2. Open "Manage Device Catalog" from Start → SIMATIC → SIMATIC PDM.
3. Navigate to PDM device driver, select device and click "OK". The driver is installed on the
6.4.3

Adding the device to the network

It is recommended to configure the FUS080 project in PDM before setting the parameters.
1. Add device to SIMATIC MODBUS network:
6.4.4

Configuring the device

In the following it is described how to configure the device by defining all sensor specific
parameters.
Note
Measurement accuracy
A correct sensor installation and a completed measurement report containing correctly
defined sensor-specific data is required to ensure optimum measurement accuracy.
 For further information, refer to the sensor operating instructions.
 For allowed inaccuracies, refer to "Sensor geometrical data" (Page 63).
34
(http://support.automation.siemens.com/WW/view/en/16889017/133100), or copy it from
supplied CD into envisaged folder and unzip the file. Check that the EDD is the version
valid for the device.
PC.
– Select "File" → "New"
Type in a project name, e.g. SONOKIT
– Right click on "Net" and select "Insert New Object" → "Modbus Net".
Your PC is now added to the Modbus Net
– Right click on "Modbus Net" and select "Insert New Object" → "Modbus Device"
– Click on "Assign" and assign the Modbus device to SITRANS FUS/E080 (Sensors →
Flow → Ultrasonic → SIEMENS AG → SITRANS FUS/E080) and click "OK".
Rename device according to application requirements (max. 32 characters).
Set up communication parameters for SIMATIC MODBUS network
– Select "Net" → "Modbus Net", right click on "Modbus net" and select "Object
Properties"
– Select "Connection" to activate IrDA
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans f us sonokitSitrans fus380Sitrans fue380

Table of Contents