Image 5-2
9. Reinstall the electronic including the mounting screw.
10.Connect the sensor connection and the sensor cable.
11.Restore the flexible strap around all wires.
12.Assemble and tighten the cable gland.
13.Remove the O-ring from lid.
14.Reinstate the lid and screw in until the mechanical stop. Wind back the lid by one turn.
15.Mount the O-ring by pulling it over the lid and tighten the lid until you feel friction from the
O-ring on both sides. Wind the lid by one quarter of a turn to seal on the O-ring.
16.Reinstate and tighten the lid lock screw.
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
Sensor terminal compartment
Connecting
5.4 Connecting the FC410