4.2.2

Time function

The Time function can be enabled (value 0) and disabled (value 1) via the bus (1 bit communication object
Disable function Time). The output operates without a delay as long as the Time function is disabled.
The following functions can be undertaken using the Time function:

Staircase lighting

You can switch, for example, between functions, e.g. function Staircase lighting (night time operation) and
normal ON/OFF switch function (daytime operation).
4.2.2.1
Staircase lighting
After the staircase lighting time T
with the value 1, the time restarts, except if the parameter Extending staircase lighting by multiple opera-
tion ["pumping up"] in
The response is the basic response of the Staircase lighting function.
Via "pumping up" – actuation of the push button several times in succession – the user can adapt the
staircase lighting to current needs. The maximum duration of the staircase lighting time can be set in the
parameters.
If the device receives a further ON telegram when the staircase lighting is switched on, the staircase light-
ing time is added to the remaining period.
90 2CDC508116D0203 | FCL/S x.6.1.1
has elapsed, the output switches off automatically. For every telegram
ON
Parameter window B: Output -
Time, p.58 is set to No (not retriggerable).