Lamp Output Load At 230 V Ac - ABB i-bus KNX FCL/S 1.6.1.1 Product Manual

Blower actuator, fcl/s x.6.1.1 series
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
Lamp output load at 230 V AC
2.1.2
Lamps
Fluorescent lamps T5/T8
Low-voltage halogen lamps
Dulux lamp
Mercury-vapor lamp
Switching capacity (switching contact)
Number of electronic ballasts
1)
(T5/T8, single element)
1)
For multiple element lamps or other types the number of electronic ballasts must be determined using the peak inrush current of the ballasts.
Device type
Application
FCL/S 1.6.1.1
Switch Blower 1f 6A/1.0*
FCL/S 2.6.1.1
Switch Blower 2f 6A/1.0*
* ... = current version number of the application. Please refer the software information on our homepage for this purpose.
Note
ETS and the current version of the device application are required for programming.
The current version of the application is available for download at www.abb.com/knx. After import into
ETS it appears in the Catalogs window under Manufacturers/ABB/Heating, Ventilation, Air condition-
ing/Ventilation actuator.
The device does not support the locking function of a KNX device in ETS. If you use a BCU code to
inhibit access to all the project devices, it has no effect on this device. Data can still be read and pro-
grammed.
10 2CDC508116D0203 | FCL/S x.6.1.1
Incandescent lamp load
Uncorrected
Parallel compensated
DUO circuit
Inductive transformer
Electronic transformer
Halogen lamps 230 V
Uncorrected
Parallel compensated
Uncorrected
Parallel compensated
Maximum peak inrush current I
p
Maximum peak inrush current I
p
Maximum peak inrush current I
p
18 W (ABB EVG 1 x 18 SF)
24 W (ABB EVG-T5 1 x 24 CY)
36 W (ABB EVG 1 x 36 CF)
58 W (ABB EVG 1 x 58 CF)
80 W (Helvar EL 1 x 80 SC)
Maximum number of
Communication objects
64
124
(150 s)
(250 s)
(600 s)
Maximum number of
group addresses
254
254
1200 W
800 W
300 W
350 W
800 W
1000 W
1000 W
800 W
800 W
1000 W
800 W
200 A
160 A
100 A
10
10
7
5
3
Maximum number of
associations
254
254