Accuracy Specifications (Excluding Current Sensors); Specifications At 50/60Hz - AEMC PEL 102 User Manual

Power energy logger
Hide thumbs Also See for PEL 102:
Table of Contents

Advertisement

5.2.3 Accuracy Specifications (excluding current sensors)

5.2.3.1 Specifications at 50/60Hz

Quantity
Frequency (f)
Phase to neutral voltage (V)
Phase to phase voltage (U)
Current (I) without current sensor *
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (PF)
Tan Φ
Active energy (Ep)
Power & Energy Logger Model PEL 102 and PEL 103
Measurement Range
42.5 to 69Hz
10 to 100V
100 to 1000V
17 to 170V
170 to 1700V
0.2 to 5% Inom
5 to 120% Inom
PF = 1
V = 100 to 1000V
I = 5 to 120% Inom
PF = [0.5 inductive ; 0.8 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Sin ϕ = 1
V = 100 to 1000V
I = 5 to 120% Inom
Sin ϕ = [0.5 inductive ; 0.5 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Sin ϕ = [0.5 inductive ; 0.5 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Sin ϕ = [0.25 inductive ; 0.25 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
V = 100 to 1000V
I = 5 to 120% Inom
PF = [0.5 inductive ; 0.5 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
PF = [0.2 inductive ; 0.2 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Tan Φ = [√3 inductive ; √3 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Tan Φ = [3.2 inductive ; 3.2 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
PF = 1
V = 100 to 1000V
I = 5 to 120% Inom
PF = [0.5 inductive ; 0.8 capacitive]
V = 100 to 1000V
I = 5 to 120% Inom
Intrinsic Uncertainty
± 0.1Hz
± 0.2% ± 0.2V **
± 0.2% ± 0.2V
± 0.2% ± 0.4V **
± 0.2% ± 0.4V
± 0.2% ± 0.02% Inom **
± 0.2% ± 0.02% Inom
± 0.5% ± 0.005% Pnom
± 0.7% ± 0.007% Pnom
± 1% ± 0.01% Qnom
± 1% ± 0.015% Qnom
± 1.5% ± 0.015% Qnom
± 3.5% ± 0.003% Qnom
± 0.5% ± 0.005% Snom
± 0.05
± 0.1
± 0.02
± 0.05
± 0.5%
± 0.6 %
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pel 103