3.7.5 Information Display Values
This screen is disabled if three minutes elapse with no activity on the Enter or Navigation buttons. The display then returns
to the Base Measurements screen.
Step
Value
<<HOOK UP>>
1
Distribution
System
Type
«PT PRIM»
2
Primary
VT
«PT SEC»
3
Secondary VT
«CT PRIM»
4
Primary
CT
«AGG.PERIOd»
5
Aggregation
period
Year
Month
6
Day
Time
<<IP Addr>>
7
IP address
<<Soft>>
Software Version
8
Serial Number
Power & Energy Logger Model PEL 102 and PEL 103
1P-2W
= 1-phase 2-wire
1P-3W
= 1-phase 3-wire
3P-3W∆3 = 3-phase 3-wire ∆ (3 current sensors)
3P-3W∆2 = 3-phase 3-wire ∆ (2 current sensors)
3P-3W02 = 3-phase 3-wire Open ∆ (2 current sensors)
3P-3W03 = 3-phase 3-wire Open ∆ (3 current sensors)
3P-3W∆B = 3-phase 3-wire ∆ balanced
3P-3WY
= 3-phase 3-wire Y (3 current sensors)
3P-3WY2 = 3-phase 3-wire Y (2 current sensors)
3P-4WY
= 3-phase 4-wire Y
3P-4WYB = 3-phase 4-wire Y balanced (fixed, voltage measurement)
3P-4WY2 = 3-phase 4-wire Y 2½
= 3-phase 4-wire ∆
3P-4W∆
3P-4WO∆ = 3-phase 4-wire Open ∆
DC-2W
= DC 2-wire
DC-3W
= DC 3-wire
DC-4W
= DC 4-wire
Displays the aggregation period in minutes (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60)
2nd number = Microprocessor firmware version
(a label is also pasted inside the PEL on the main board)
Units
V
V
A
Displays the date/time
Scrolling IP address
1st number = DSP firmware version
Scrolling serial number
Table 8