3.6.5 3-Phase 4-Wire ∆
High Leg configuration. No Potential Transformer (Voltage Transformer) is connected; the installation under test is sup-
posed to be a low voltage distribution system.
3.6.5.1 3-Phase 4-Wire ∆
For 3-Phase 4-Wire
measurements and using three current
sensors:
Connect the terminal N test lead to the neutral conductor
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed
towards the load. This ensures proper phase angle for power
measurements and other phase sensitive measurements.
3.6.5.2 3-Phase 4-Wire Open ∆
For 3-Phase 4-Wire Open
rent sensors:
Connect the terminal N test lead to the neutral conductor
Connect the terminal V1 test lead to the L1 phase
conductor
Connect the terminal V2 test lead to the L2 phase
conductor
Connect the terminal V3 test lead to the L3 phase
conductor
Connect the terminal I1 current probe to the LI phase
conductor
Connect the terminal I2 current probe to the L2 phase
conductor
Connect the terminal I3 current probe to the L3 phase
conductor
Ensure that the current arrow on the sensor is directed towards
the load. This ensures proper phase angle for power measure-
ments and other phase sensitive measurements.
28
measurements and using three cur-
L2
L1
L3
N
V1
V2
V3
N
Figure 24
L2
L1
L3
N
V1
V2
V3
N
Figure 25
Power & Energy Logger Model PEL 102 and PEL 103
L1
L2
L3
N
I1
I2
I3
L1
L2
L3
N
I1
I2
I3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pel 103

Table of Contents