Configuration (Pel 103) - AEMC PEL 102 User Manual

Power energy logger
Hide thumbs Also See for PEL 102:
Table of Contents

Advertisement

3.7.6 Configuration
The Configuration mode lets you select the distribution system (hook up), voltage ratio and primary current value, primary
CT value, and aggregation period on the Model PEL 103 instrument. This screen is inactive when:
The PEL is recording (pending or in progress).
Configuration via the DataView PEL Control Panel is in progress.
The button is locked through an option in the PEL Control Panel.
Configuration is disabled by the Control button on the front panel.
NOTE: To avoid conflicts, when the Configuration screen is displayed, configuration through the PEL Control Panel
is disabled. You also cannot start a recording session with the Control button while the Configuration screen is
displayed. If you attempt to use the Control button while it is locked by the PEL Control Panel, the Bluetooth ON/
OFF indicator and the REC START/STOP light will flash twice simultaneously. The instrument will then continue its
operation with no changes taking effect.
To change configuration settings on the Model PEL 103, enter the Configuration mode and do the following:
1. Scroll to the setting you want to change using the down arrow ▼ and up arrow ▲ buttons.
2. Press the Enter
3. Use the Navigation
4. When the desired value appears, press the Enter button. The setting will stop blinking.
As with the Information screen, the Configuration screen is disabled if three minutes elapse with no activity on the Enter or
arrow buttons. The display then returns to the Base Measurements screen.
Step
Value
<<HOOK UP>>
1
Distribution
System
Type
«PT PRIM»
2
Primary
VT
40
(PEL 103)
button. The displayed setting will start blinking.
button to scroll through the allowable values for the setting.
1P-2W
= 1-phase 2-wire
1P-3W
= 1-phase 3-wire
3P-3W∆3
=
3-phase 3-wire ∆ (3 current sensors)
3P-3W∆2 = 3-phase 3-wire ∆ (2 current sensors)
3P-3W02
=
3-phase 3-wire Open ∆ (2 current sensors)
3P-3W03 = 3-phase 3-wire Open ∆ (3 current sensors)
3P-3W∆B =
3-phase 3-wire ∆ balanced
3P-3WY = 3-phase 3-wire Y (3 current sensors)
3P-3WY2
=
3-phase 3-wire Y (2 current sensors)
3P-4WY = 3-phase 4-wire Y
3P-4WYB =
3-phase 4-wire Y balanced (fixed, voltage measurement)
3P-4WY2
=
3-phase 4-wire Y 2½
3P-4W∆ = 3-phase 4-wire ∆
3P-4WO∆ =
3-phase 4-wire Open ∆
DC-2W
= DC 2-wire
DC-3W
= DC 3-wire
DC-4W
= DC 4-wire
Units
V
Power & Energy Logger Model PEL 102 and PEL 103