A.5.3 Current vs Voltage Phase Order
Distribution
System
Single phase
(1-Phase 2-Wire)
Split phase
(1-Phase 3-Wire)
3-Phase 3-Wire ∆
[2 current sensors]
3-Phase 3-Wire Open-∆
[2 current sensors]
3-Phase 3-Wire Y
[2 current sensors]
3-Phase 3-Wire ∆
3-Phase 3-Wire Open-∆
3-Phase 3-Wire Y
3-Phase 3-Wire ∆
balanced
3-Phase 4-Wire Y
3-Phase 4-Wire Y
balanced
3-Phase 4-Wire Y 2½
3-Phase 4-Wire ∆
3-Phase 4-Wire Open-∆
DC 2-Wire
DC 3-Wire
DC 4-Wire
Power & Energy Logger Model PEL 102 and PEL 103
Current Phase
Abbreviation
Order
1P-2W
Yes
1P -3W
Yes
3P-3W∆2
Yes
3P-3WO2
3P-3WY2
3P-3W∆3
3P-3WO3
Yes
3P-3WY3
3P-3W∆B
Yes
3P-4WY
Yes
3P-4WYB
Yes
3P-4WY2
Yes
3P-4W∆
Yes
3P-4WO∆
DC-2W
DC-3W
DC-4W
ϕ
(I1, V1) = 0° ± 60° for load
(I1, V1) = 180° ± 60° for source
ϕ
[ϕ (I1, V1), ϕ (I2, V2)] = 0° ± 60° for load
[ϕ (I1, V1), ϕ (I2, V2)] = 180° ± 60° for source
[ϕ (I1, U12), ϕ (I3, U31)] = 30° ± 60° for load
[ϕ (I1, U12), ϕ (I3, U31)] = 210° ± 60° for source
No I2 current sensor
[ϕ (I1, U12), ϕ (I2, U23), ϕ (I3, U31)] = 30° ± 60° for load
[ϕ (I1, U12), ϕ (I2, U23), ϕ (I3, U31)] = 210° ± 60° for source
(I3, U12) = 90° ± 60° for load
ϕ
(I3, U12) = 270° ± 60° for source
ϕ
[ϕ (I1, V1), ϕ (I2, V2), ϕ (I3, V3)] = 0° ± 60° for load
[ϕ (I1, V1), ϕ (I2, V2), ϕ (I3, V3)] = 180° ± 60° for source
(I1, V1) = 0° ± 60° for load
ϕ
(I1, V1) = 180° ± 60° for source
ϕ
[ϕ (I1, V1), ϕ (I3, V3)] = 0° ± 60° for load
[ϕ (I1, V1), ϕ (I3, V3)] = 180° ± 60° for source
No V2
[ϕ (I1, U12), ϕ (I2, U23), ϕ (I3, U31)] = 30° ± 60° for load
[ϕ (I1, U12), ϕ (I2, U23), ϕ (I3, U31)] = 210° ± 60° for source
No
No
No