Test Of The Boundary Between Zone 1 And Zone 2, Which Is Defined By The Parameter Reachz1 - ABB Relion 670 Series Commissioning Manual

Line differential protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
frequency of I
Expected result: start of the protection function and trip in zone 2, when trip conditions are
fulfilled.
11.4.12.3
Test of the boundary between zone 1 and zone 2, which is defined by the
parameter
The trajectory of the impedance traverses the lens characteristic in zone 2
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/OutOfStep(78,Ucos)/
OOSPPAM(78,Ucos):1/Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
ts
EQUATION14065 V1 EN-US
V
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
∠I
50s
frequency of I
It
fs
EQUATION14062 V1 EN-US
∠I
tfs
frequency of I
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according to the
injected quantities and that ROTORANG is close to 3.14 rad. For this particular injection
the service values are:
Note that these values identify a point inside the lens characteristic, in the Zone 2, that is close
to the boundary between zone 1 and zone 2. The START is issued, but no TRIP is performed.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature of
test sets.
146
= 49.5 Hz
tfs
ReachZ1
V
VT s
,
1 1
.
1 1 1435
.
V
=
×
×
=
×
t RZ
,
1
V
,
VT p
ForwardX
=
 =
arctan
ts
ForwardR
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
I
9000
CTp
= 0º
= 50 Hz
50s
I
1
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
= 0º
= 50 Hz
tfs
VOLTAGE = 1.58 kV
CURRENT = 20918 A
R = 1.08%
X = 7.85%
ROTORANG = -3.04 rad
© Copyright 2017 Hitachi Power Grids. All rights reserved
0 1
.
11 44
.
V
×
=
13 8
.
59 33
.
 =
arctan
82. . 14°
8 19
.
= .
1 162
A
1 162
.
A
=
1MRK 505 378-UEN Rev. H
GUID-BE180E07-7D4B-4842-81FB-244DE8897430 v1
GUID-17F6AC8D-1F57-4245-A61D-776D469DD153 v1
GUID-3D42E43D-873E-4271-9AAF-3B2789FF3B17 v1
(Equation 40)
(Equation 41)
(Equation 42)
(Equation 43)
GUID-53964189-42E4-4C4B-BFCD-64888BA938EF v1
Line differential protection RED670
Commissioning manual