1.8
Setting Measurement Conditions (Scan interval,
A/D integrate, etc.)
1.8.1

Setting the Scan Interval

Path
Description
1.8.2

Setting the Over-range Detection Method

Path
Description
1-90
Set the scan interval, A/D integrate, measurement groups, etc.
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings
Web application: Config. tab > Measurement settings > Scan interval
Hardware configurator: Measurement settings > Scan interval
Scan interval
Setup Item
Scan interval
1 Cannot be specified if an electromagnetic relay type (type suffix code -T1) analog input module
is in use (configured).
2 2 s if an electromagnetic relay type analog input module is in use.
3 Cannot be specified if a low withstand voltage relay type (type suffix code -L1) analog input
module is in use (configured).
Scan interval
Set the scan interval. The scan intervals that you can set are displayed depending on the
installed modules.
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings
Web application: Config. tab > Measurement settings > Over-range
Hardware configurator: Measurement settings > Over-range
Over-range
Setup Item
Value on over-range
Value on over-range
Set how to detect over-range values on linearly scaled or square-rooted I/O channels.
In either case, +over range occurs if the value excluding the decimal point exceeds 99999
and –over range if it falls below –999999.
Options
Description
Free
The value is set to –over range if the value is less than –5% of the measurable
span range and +over range if the value is greater than 105%.
Over
The value is set to –over range if the value is less than –5% of the span setting
(Linear scaling or , Square root span) and +over range if the value is greater
than 105%.
Example: If the linear scaling scale is 0.0 to 200.0, a value less than –10.0
results in a –over range, and a value greater than 210.0 results in a +over
range.
Selectable Range or Options
1, 3
1, 3
100ms
, 200ms
, 500ms
Selectable Range or Options
Free, Over
Default Value
1
2
, 1s, 2s, 5s
1s
Default Value
Over