1.12 Configuring the Report Function (/MT option)
1.12.2

Setting the Channels to Output Reports

Path
Description
Explanation
1-118
GX/GP: MENU key > Browse tab > Setting > Setting menu Report settings > Report
channel settings
Web application: Config. tab > Report settings > Report channel settings
Hardware configurator: Report settings > Report channel settings
Setup Item
Report channel number
Report channel number
Select the report channel number. The GX/GP generates reports in order by this number.
Report channel
Setup Item
Channel type
1
Channel no
1
Sum scale
1 Appears when the channel type is not set to Off.
Channel type
Set the channel type to assign to the report channel.
Channel no
Set the channel number to assign to the report channel. All channels can be assigned, but
reports are not created for channels set to Skip or Off even if they are assigned.
Sum scale
Set the sum scale to match the unit of the measured values.
Example: If the unit of the measured value is "m
Off: The measured data is summed as-is once per scan interval.
Unit of Sum Computation
In sum computation, data is summed over the scan interval. However, for flow values that
have units /s, /min, /h, or /day a simple summation results in the actual value not matching
the computed result, because the scan interval and the unit of the input values are different.
In such cases, set the sum scale to match the unit of the input value. In effect, the sum value
with the same unit as that of the input value is computed.
For example, if the scan interval is 2 s, and the input value is 100 m
summation would add 100 every 2 s resulting in 3000 after one minute. However, if the sum
scale is set to /min, then 2 s/60 s is multiplied every scan interval before the value is added
giving a result that has an m
The following converting equations are used to compute the sum. The scan interval unit is
seconds.
Off:Σ(measured data every scan interval)
/s: Σ(measured data every scan interval) × scan interval
/min: Σ(measured data every scan interval) × scan interval/60
/h: Σ(measured data every scan interval) × scan interval/3600
/day: Σ(measured data every scan interval) × scan interval/86400
Selectable Range or Options
GX20/GP20: 1 to 60
GX10/GP10: 1 to 50
Selectable Range or Options
I/O channel, Math channel, Communication
channel, Off
Channels that you can set
Off, /s, /min, /h, /day
3
/min," select /min.
3
/min unit.
Default Value
1
Default Value
3
/min, a simple
IM 04L51B01-01EN