Supported Commands - YOKOGAWA SMARTDAC+ GX10 User Manual

Paperless recorder
Hide thumbs Also See for SMARTDAC+ GX10:
Table of Contents

Advertisement

1.27 Using the DARWIN Compatible Communication Function (Release number 2 and later)
1.27.2

Supported Commands

1-218
The commands supported by the DARWIN compatible communication function are as
follows.
Instantaneous Data Output Commands
Command
Description
EF
Outputs measured data and math data in binary format.
EL
Outputs unit and decimal point information of a specified channel in ASCII
format.
EB
Sets the byte output order.
ESC+T Command
If a "Esc+T" command is received, time-synchronized measured value and math value are
held in the local buffer until the next "Esc+T" command is received.
Command
Description
Esc+T
Prepares to output the data selected with the TS command.
Setting Commands
Command
Description
SR
Sets the range.
SN
Sets the unit (scale unit).
SA
Sets an alarm.
SD
Sets the date and time.
SV
Sets moving average.
CM
Sets math input data (option).
SR Command Parameters
If a setting parameter that the GX/GP does not support is received, a negative response is
returned.
Item
Mode
Range
Module
Commands Applicable to RS-422-A/RS-485 Only (Release number 2 (version 2.02) and
later)
Command
Description
Esc+O
Open Command (address a communication destination)
EXC+C
Close Command (close the addressed state of a device)
Data Output Request Commands
Command
Parameter
TS
0: Measured data
1: Setting parameters
2: Unit information
5: System configuration information
9: Setup mode setting data output
FM
0: Measured data (ASCII)
1: Math data (binary)
2: Math data (ASCII)
3: Math channel (binary)
LF
CF
VF
BO
1
Esc+S
1 Release number 2 (version 2.02) and later
Description
RRJC
PT2, JPT2, PT2S, JPT2S, GATE
AC, STRAIN
Description
Selects the talker output data.
Selects the output format of
measured/math data.
Sets the output channel for the
setting data output, unit, and
decimal place information.
Sets the system configuration data
format.
Relay status output request
Sets the byte output order.
Status byte output command
IM 04L51B01-01EN