Configuring Di Channels (Digital Input Channels) - YOKOGAWA SMARTDAC+ GX10 User Manual

Paperless recorder
Hide thumbs Also See for SMARTDAC+ GX10:
Table of Contents

Advertisement

1.3
Configuring DI Channels (Digital input channels)
1.3.1
Setting the Range
Path
Description
1-40
Set the input range, alarm, and display conditions of DI channels (including the DI channels
of DI/DO modules).
To use the DI module as a remote control input, set the operation mode of the module to
Remote.
Refer to page 1-91 in section 1.8.3, "Setting the Operation Mode of a Module".
Set the remote control action using event action.
"Configuring the Event Action Function".
GX/GP: MENU key > Browse tab > Setting > Setting menu DI channel settings > Range
Web application: Config. tab > DI channel settings > Channel range (display example:
0501-0516) > Range
Hardware configurator: DI channel settings > Channel range (display example: 0501-0516)
> Range
Setup Item
First-CH
Last-CH
First-CH, Last-CH
Set the target channels. The channels that you can specify appear depending on the module
configuration.
Range
Setup Item
Type
Span Lower
DI
Pulse
Span Upper
DI
Pulse
Calculation
1
Reference channel
1 Appears when Calculation is set to Delta.
2 You can set this when the GM10 has the /MT option and the operation mode is set to Normal.
3 This is fixed to Off when the Type is set to Pulse.
Type
Set the input type.
Options
Description
Skip
Not measured.
DI
Displays contact input or voltage input signals by mapping them to 0% or 100% of the
display range.
Pulse
Counts pulses.
Maximum measurement pulse cycle: 250 Hz (chattering filter for pulse input: off)
For details on the chattering filter for pulse input, see page 1-93 in section 1.8.6, "Setting
the Chattering Filter (DI module) for Pulse Input".
Span Lower, Span Upper
Set the input range.
Refer to page 1-125 in section 1.15,
Selectable Range or Options
DI channel
DI channel
Selectable Range or Options
2
Skip, DI, Pulse
0, 1
Delta: –1 to 1
0 to 999999 (decimal place: 0)
0, 1
Delta: –1 to 1
0 to 999999 (decimal place: 0)
3
Off
, Delta, Linear scaling
Value (I/O channel)
125 Hz (chattering filter for pulse input: on)
Default Value
Default Value
DI
0
0
1
1250
Off