4.5.2

Modbus Server/Slave Function

4.5.3
Register Assignments (Shared with the Modbus server/slave function)
IM 04L51B01-01EN
Function
The GX/GP supports the following functions.
Function Code Function
1
Read the coil status
(0xxxx)
2
Read the input relay
status (1xxxx, 1xxxxx)
3
Read the hold register
(4XXXX, 4XXXXX)
4
Read the input register
(3XXXX, 3XXXXX)
5
Change the single coil
status
(0xxxx)
6
Write to a single hold
register (4xxxx, 4xxxxx)
1
8
Loop-back test
15
Change the coil status
(0xxxx)
16
Write to the hold register
(4XXXX, 4XXXXX)
1 Loopback test is only for serial communication.
Input Register
Unit
GX/GP main unit I/O channel
I/O channel
(continuous area)
Math channel
(A001 to 100)
Math channel
(A101 to 200)
GX/GP status
Expandable I/O
Unit 1
I/O channel
Unit 2
I/O channel
Unit 3
I/O channel
Unit 4
I/O channel
4.5 Modbus Function and Register Assignments
Operation
The client (master) device reads the coil status of the GX/
GP.
The client (master) device reads the input relay status of
the GX/GP.
The client (master) device reads the GX/GP data.
The client (master) device reads the I/O, math, alarm,
time data from the GX/GP.
The client (master) device changes the single coil status
(off/on) of the GX/GP.
The client (master) device writes to a single hold register
of the GX/GP.
The master device performs a GX/GP loopback test.
The client (master) device changes the coil status (off/on)
of the GX/GP.
The client (master) device writes to the GX/GP
communication channels.
Type
Number
I/O data
300001 to 301000 32-bit signed integer
301001 to 302000 32-bit floating point
302001 to 302500 16-bit signed integer
Status information
302501 to 303000 16-bit signed integer
I/O data
304001 to 304200 32-bit signed integer
304201 to 304400 32-bit floating point
304401 to 304500 16-bit signed integer
Status information
304501 to 304600 16-bit signed integer
Math data
305001 to 305200 32-bit signed integer
305201 to 305400 32-bit floating point
305401 to 305500 16-bit signed integer
Status information
305501 to 305600 16-bit signed integer
Math data
306001 to 306200 32-bit signed integer
306201 to 306400 32-bit floating point
306401 to 306500 16-bit signed integer
Status information
306501 to 306600 16-bit signed integer
308001 to 308007 16-bit signed integer
I/O data
310001 to 311000
311001 to 312000
312001 to 312500 16-bit signed integer
Status information 312501 to 313000 16-bit signed integer
I/O data
315001 to 316000 32-bit signed integer
316001 to 317000 32-bit floating point
317001 to 317500 16-bit signed integer
Status information 317501 to 318000 16-bit signed integer
I/O data
320001 to 321000 32-bit signed integer
321001 to 322000 32-bit floating point
322001 to 322500 16-bit signed integer
Status information 322501 to 323500 16-bit signed integer
I/O data
325001 to 326000 32-bit signed integer
326001 to 327000 32-bit floating point
327001 to 327500 16-bit signed integer
Status information 327501 to 328000 16-bit signed integer
GX/GP Register
Data Type
32-bit signed integer
32-bit floating point
Continued on next page
4-13