1.8.3

Setting the Operation Mode of a Module

Path
Description
Explanation
IM 04L51B01-01EN
1.8 Setting Measurement Conditions (Scan interval, A/D integrate, etc.)
GX/GP: MENU key > Browse tab > Setting > Setting menu Measurement settings >
Select unit Main unit or Unit1 to 6 > Module 0 to 9
Web application: Config. tab > Measurement settings > Module settings
Hardware configurator: Measurement settings > Module settings
1 The module numbers that appear depend on the GX/GP module configuration.
AI Modules
Operation mode
Setup Item
Selectable Range or Options
2
Operation mode
2ch Only, Low noise mode; 10ch Normal mode
2 Fixed to 10ch mode for the electromagnetic relay type (Type suffix code -T1) or low withstand
voltage relay type (Type suffix code -L1) analog input module.
Operation mode
Set the operation mode to use. For details on the operation modes, see the explanation.
DI Modules
Operation mode
Setup Item
Selectable Range or Options
Operation mode
Remote, Normal
Operation mode
Set the operation mode to use. For details on the operation modes, see the explanation.
2ch Mode and 10ch Mode (AI modules)
In 10ch mode, measurement is possible on CH1 to CH10.
In 2ch mode, measurement is possible only on CH1 and CH2. (CH3 to CH10 are fixed to
Skip.)
In 10ch mode, when the scan interval is set to 100 ms or 200 ms, the A/D integration time
is fixed at 1.67 ms. This prevents power frequency noise from being eliminated, causing
measured values to wobble (especially for temperature).
In 2ch mode, when the scan interval is 100 ms or 200 ms, the A/D integration time is
16.67 ms or 20 ms. This allows power frequency noise to be eliminated.
Note that the selectable A/D integration times vary depending on the 2ch/10ch mode and
scan interval settings.
Normal and Remote (DI modules)
Specify Remote to use the DI module as a remote control input.
When there are multiple DI modules, only one of them can be set to Remote.
Remote can only be specified for a DI module or DI/DO module installed in the GX/GP main
unit.
For normal DI input, specify Normal.
When using Event action, set to Remote.
For details on report control using event action, see page 1-125 in section 1.15,
"Configuring the Event Action Function".
Operation mode
DI input
1
Normal
DI Channel
0
Remote
DI Channel
1
Default Value
10ch Normal mode
Default Value
Normal
DI Record
DI Record
Remote control
Event Action Setting
1
2
3
4
5
App
Index
1-91