Setting Calibration Correction (Linearizer Approximation, Linearizer Bias, Correction Factor* (Release Number 3 And Later)) - YOKOGAWA SMARTDAC+ GX10 User Manual

Paperless recorder
Hide thumbs Also See for SMARTDAC+ GX10:
Table of Contents

Advertisement

1.2 Configuring AI Channels (Analog (including DI) input) channels and AI (mA) channels
1.2.4
Setting Calibration Correction (Linearizer approximation, linearizer bias,
Correction Factor* (release number 3 and later))
Path
Description
1-36
* Only for the /AH option
GX/GP: MENU key > Browse tab > Setting > Setting menu AI channel settings or AI (mA)
channel settings > Calibration correction
Web application: Config. tab > AI channel settings or AI (mA) channel settings >
Channel range (display example: 0001-0010) > Calibration correction
Hardware configurator: AI channel settings or AI (mA) channel settings > Channel range
(display example: 0001-0010) > Calibration correction
Setup Item
First-CH
Last-CH
First-CH, Last-CH
Set the target channels. You can set consecutive channels whose range is set to the same
value as the first channel.
Mode
Setup Item
Mode
1
Number of set points
1 Appears when the mode is not set to Off.
Mode
Set the correction mode when performing calibration correction.
When the range is set to DI or Skip, the mode is fixed to Off.
Number of set points
Set the number of points that make up the segments (including the start and end points).
1 to 12 (When the mode is set to linearizer approximation or
*
linearizer bias)
Setup Item
Linearizer input
Linearizer output
Execution of the input
measurement
* The number of displayed points varies depending on the number of set points.
Linearizer input, Linearizer output
Enter the value of the set point. For linearizer input, set a value that is greater than the
previous value.
Selectable Range of Linearizer Input and Output Values
• Channels using linear scaling
–999999 to 999999 (the decimal place is the same as that for the scale value)
• Other channels
Values inside parentheses are examples for the 2 V range.
Linearizer approximation
Selectable range of linearizer input: Measurable range (–2.0000 to 2.0000 V)
Selectable range of linearizer output: Display range (–2.2000 to 2.2000 V)
Linearizer bias
Selectable range of linearizer input: Measurable range (–2.0000 to 2.0000 V)
Selectable range of linearizer output: Measurement span width ± 100% (–4.0000 to
4.0000 V)
Selectable Range or Options
AI channel
AI channel
Selectable Range or Options
Off, Linearizer Approximation, Linearizer Bias,
Correction Factor
2 to 12
Selectable Range or Options
–999999 to 999999
–999999 to 999999
Default Value
Default Value
Off
2
Default Value
IM 04L51B01-01EN