Setting Internal Switches - YOKOGAWA SMARTDAC+ GX10 User Manual

Paperless recorder
Hide thumbs Also See for SMARTDAC+ GX10:
Table of Contents

Advertisement

1.19.5
Setting Internal Switches
Path
Description
IM 04L51B01-01EN
1.19 Configuring System Settings (Time zone, display language, status relay, etc.)
GX/GP: MENU key > Browse tab > Setting > Setting menu System settings > Internal
switch settings
Web application: Config. tab > System settings > Internal switch settings
Hardware configurator: System settings > Internal switch settings
Setup Item
First number
Last number
First number
Select the first internal switch number that you want to set.
Last number
Select the last internal switch number that you want to set.
Internal switch
Setup Item
Type
1
And/Or
1 Appears when the type is not set to Alarm.
Type
Set the item to assign to the internal switch.
Options
Alarm
Manual
And/Or
Set the internal switch operation conditions when multiple alarm outputs are assigned to the
switch.
When the channel 1 alarm output and channel 2 alarm output are assigned, And and Or
operations are as shown in the figure below.
When set to AND
CH1 alarm
CH2 alarm
On
Internal switch
S001
Selectable Range or Options
1 to 100
1 to 100
Selectable Range or Options
Alarm, Manual
AND, OR
Description
Assigns the internal switch as an alarm output destination.
Specify this to manually operate with the "OCmdRelay" communication
command.
When set to OR
On
On
Default Value
1
1
Default Value
Alarm
App
OR
Index
1-171
1
2
3
4
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartdac+ gp10Smartdac+ gx20Smartdac+ gp20