Advanced Operation (Various Settings And Operation); Setting Measurement And Recording Conditions; Setting Alarms - YOKOGAWA GX60 User Manual

Paperless recorder
Table of Contents

Advertisement

This section explains how to change various settings.
Before you change settings, stop recording and computation.

Advanced Operation (Various settings and operation)

Setting Measurement and Recording
Conditions
Configuring the type of data to record to display data, the
scan interval to 2 s, and the trend interval to 1 min.
Setting the Type of Data to Record
Path
MENU key > Browse tab > Setting >
Setting menu > Recording Settings >
Basic settings
1
Tap File type > Display.
2
Tap Save.
You can set the file type to record only the data that
suits your purpose. For example, you can record
detailed data or record data only when alarms occur.
For details, see the User's Manual (IM 04L51B01-
01EN).
Setting the Scan Interval
Path
MENU key > Browse tab > Setting >
Setting menu > Measurement settings >
Scan interval
1
Tap Scan interval > 2s.
2
Tap Save.
42
Power Specialties, Inc. | www.powerspecialties.com | (816) 353-6550
Setting the Trend Interval
1
1
2
2
On channel 1 of slot 0, set the high limit alarm at the alarm
value of 150°C.
1
1
2
3
4
2
5
6
Operation complete
Path
MENU key > Browse tab > Setting >
Setting menu > Display settings > Trend
interval
Tap Trend interval [/div] > 1 min.
Tap Save.

Setting Alarms

Path
MENU key > Browse tab > Setting >
Setting menu > AI channel settings > Alarm
Tap First-CH > 0001.
Check that Last-CH is 0001.
Tap Level1 > On.
Tap Type > H.
Tap Value, and enter 150.0.
Tap Save.
1
2
Operation complete
1
2
3
4
5
6
Operation complete
IM 04L51B01-02EN