Functions, Settings, Information
F.2 Settings
F.2
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Additional Settings".
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr. Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
BLK f out of r
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
T TRIP DELAY
0A
T DROPOUT DELAY Flx
0A
DROPOUT RATIO
0A
DROPOUT RATIO
201
CT Starpoint
386
Function
C
Setting Options
Flx
OFF
ON
Alarm Only
Flx
3-phase
1-phase
no reference
Flx
YES
NO
Flx
Please select
Current
dV/dt rising
dV/dt falling
Binary Input
Flx
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Flx
Exceeding
Dropping below
Flx
Ia
Ib
Ic
In
In sensitive
In2
Flx
1A
0.03 .. 40.00 A
5A
0.15 .. 200.00 A
Flx
1A
0.03 .. 40.00 A
5A
0.15 .. 200.00 A
Flx
0.001 .. 1.500 A
Flx
2.0 .. 200.0 V
Flx
1A
0.5 .. 10000.0 VAR
5A
2.5 .. 50000.0 VAR
Flx
15 .. 100 %
Flx
4 .. 100 V/s
Flx
0.00 .. 3600.00 sec 1.00 sec
0.00 .. 60.00 sec
Flx
0.70 .. 0.99
Flx
1.01 .. 3.00
P.System Data
towards Line
1
towards Busbar
Default Setting
Comments
OFF
Flexible Function
3-phase
Mode of Operation
YES
Block while Freq. is out of
range
Please select
Selection of Measured
Quantity
Fundamental
Selection of Measure-
ment Method
Exceeding
Pickup with
Ia
Current
2.00 A
Pickup Threshold
10.00 A
2.00 A
Pickup Threshold
10.00 A
0.100 A
Pickup Threshold
110.0 V
Pickup Threshold
200.0 VAR
Pickup Threshold
1000.0 VAR
20 %
Pickup Threshold
60 V/s
Pickup Threshold
Trip Time Delay
0.00 sec
Dropout Time Delay
0.95
Dropout Ratio
1.05
Dropout Ratio
towards Line
CT Starpoint
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016