Functions
2.1 General
Addr.
Parameter
112
Charac. Phase
113
Charac. Ground
117
Coldload Pickup
122
InrushRestraint
127
50 1Ph
131
Sens. Gnd Fault
133
INTERM.EF
140
46
141
48
142
49
143
66 #of Starts
144
LOAD JAM PROT.
170
50BF
171
79 Auto Recl.
30
Setting Options
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
Log. inverse A
Log. Inverse B
Disabled
with Ignd
with 3I0
with Ignd,sens.
Disabled
TOC ANSI
TOC IEC
Definite Time
Disabled
Enabled
Disabled
No ambient temp
With amb. temp.
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
enabled w/ 3I0>
Disabled
Enabled
Default Setting
Comments
Definite Time
50/51
Definite Time
50N/51N
Disabled
Cold Load Pickup
Disabled
2nd Harmonic Inrush Restraint
Disabled
50 1Ph
Disabled
(sensitive) Ground fault
Disabled
Intermittent earth fault protection
Disabled
46 Negative Sequence Protection
Disabled
48 Startup Time Supervision for
Motors
Disabled
49 Thermal Overload Protection
Disabled
66 Startup Counter for Motors
Disabled
Load Jam Protection
Disabled
50BF Breaker Failure Protection
Disabled
79 Auto-Reclose Function