In-rush restraint with second harmonic current quantities
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recog-
nized
Detection of cold load condition via circuit breaker position or current threshold
Activation via automatic reclosure (AR) is possible
Activation also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive or insensitive ground current transformer
Suitable as differential protection that includes the neutral point current on transformer side, generator
side or motor side or for a grounded reactor set
As tank leakage protection against abnormal leakage currents between transformer tanks and ground.
Negative Sequence Protection 46
Evaluation of the negative sequence component of the currents
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common
standards are available for 46-TOC.
Motor Starting Protection 48
Inverse time tripping characteristic based on an evaluation of the motor starting current
Definite time delay for blocked rotor.
Motor Restart Inhibit 66, 86
Approximate computation of the rotor overtemperature
Startup is permitted only if the rotor has sufficient thermal reserves for a complete startup
Disabling of the start inhibit is possible if an emergency startup is required.
Load Jam Protection for Motors 51M
Protection of motors during sudden rotor blocking
Evaluation of the positive sequence system of phase currents
Evaluation of the circuit breaker switching state
Blocking of function during motor standstill and during motor startup
Thermal Overload Protection 49
Thermal profile of energy losses (overload protection has full memory capability)
True r.m.s. calculation
Adjustable thermal warning element
Adjustable alarm level based on current magnitude
Additional time constant setting for motors to accommodate the motor at standstill
Integration of ambient temperature or coolant temperature is possible via external temperature sensors
and RTD-Box.