In-rush restraint with second harmonic current quantities
•
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
•
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are recog-
nized
•
Detection of cold load condition via circuit breaker position or current threshold
•
Activation via automatic reclosure (AR) is possible
•
Activation also possible via binary input.
Single-Phase Overcurrent Protection
•
Evaluation of the measured current via the sensitive or insensitive ground current transformer
•
Suitable as differential protection that includes the neutral point current on transformer side, generator
side or motor side or for a grounded reactor set
•
As tank leakage protection against abnormal leakage currents between transformer tanks and ground.
Negative Sequence Protection 46
•
Evaluation of the negative sequence component of the currents
•
Two definite-time elements 46-1 and 46-2 and one inverse-time element 46-TOC; curves of common
standards are available for 46-TOC.
Motor Starting Protection 48
•
Inverse time tripping characteristic based on an evaluation of the motor starting current
•
Definite time delay for blocked rotor.
Motor Restart Inhibit 66, 86
•
Approximate computation of the rotor overtemperature
•
Startup is permitted only if the rotor has sufficient thermal reserves for a complete startup
•
Disabling of the start inhibit is possible if an emergency startup is required.
Load Jam Protection for Motors 51M
•
Protection of motors during sudden rotor blocking
•
Evaluation of the positive sequence system of phase currents
•
Evaluation of the circuit breaker switching state
•
Blocking of function during motor standstill and during motor startup
Thermal Overload Protection 49
•
Thermal profile of energy losses (overload protection has full memory capability)
•
True r.m.s. calculation
•
Adjustable thermal warning element
•
Adjustable alarm level based on current magnitude
•
Additional time constant setting for motors to accommodate the motor at standstill
•
Integration of ambient temperature or coolant temperature is possible via external temperature sensors
and RTD-Box.
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Introduction
1.3 Characteristics
23