Siemens SIPROTEC 4 7SJ61 Manual page 249

Multi-funktional protective relay with bay controller
Table of Contents

Advertisement

Input/Output Board A–I/O-2 for 7SJ61.../FF
The layout of the printed circuit board for the input/output board A–I/O-2 is illustrated in the following figure.
The set nominal currents of the current input transformers and the selected operating voltage of binary inputs
BI4 to BI11 are checked.
[ein-ausgabebgr-ai-o2-ff-20070320, 1, en_US]
Figure 3-10
The jumpers X60 to X63 must all be set to the same rated current, i.e. one jumper (X61 to X63) for each input
transformer and in addition the common jumper X60. The jumper X64 determines the rated current for the
input Ι
and may thus have a setting that deviates from that of the phase currents.
N
Jumpers X80 to X85 are irrelevant for 7SJ61 devices.
Jumpers X21 to X28 do not exist in device versions 7SJ610*-.
SIPROTEC 4, 7SJ61, Manual
C53000-G1140-C210-6, Edition 05.2016
Input/output module A–I/O-2 for devices (releases .../FF and higher) with representation of the
jumper settings required for the board configuration
Mounting and Commissioning
3.1 Mounting and Connections
249

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents